Series SGHP(M) · 600–4200. Cooling 535–3,664 kW, heating 577–4,189 kW. Semi-hermetic screw, R22, 380 V / 3 ph / 50 Hz.

Technical data

Series & sizesSGHP(M) · 600–4200
Cooling capacity535–3,664 kW
Heating capacity577–4,189 kW
Water flow92–630 m³/h
CompressorSemi-hermetic screw
RefrigerantR22
Power supply380 V / 3 ph / 50 Hz
DimensionsL 3,560–5,410 · W 1,370–2,680 · H 1,470–3,235 mm
Weight5,000–15,100 kg

Figures are catalogue data at nominal conditions. Confirm the exact model on the datasheet before ordering.

Model data

Cooling duty

Chilled water 12/7 °C · cooling water 18/29 °C
SizeCooling capacitykWPower input (cooling)kWLoad-side flowm³/hSource-side flowm³/h
600535919249
80072211612466
1,00088714815381
1,2001,07118218498
1,6001,445232248131
2,0001,774296305162
3,1002,723444468248
3,7003,206520551291
4,2003,664588630332

Heating duty

Chilled water 15/7 °C · hot water 40/45.5 °C
SizeHeating capacitykWPower input (heating)kWLoad-side flowm³/hSource-side flowm³/h
6005771259249
80081116512466
1,00096620515381
1,2001,15525118498
1,6001,621331248131
2,0001,932411305162
3,1003,109632468248
3,7003,656741551291
4,2004,169838630332

Unit data

Compressors, charge, steps, connections, sound and weight
SizeCompressorsRefrigerant chargekgCapacity steps%Pipe connectionsDNSound pressuredB(A)Weightkg
600114050–75–100125795,000
800119550–75–100150805,600
1,000124050–75–100150816,500
1,2002140×225–37.5–50–62.5–75–87.5–100150807,000
1,6002195×225–37.5–50–62.5–75–87.5–100200807,500
2,0002240×225–37.5–50–62.5–75–87.5–100200817,780
3,1002350×225–37.5–50–62.5–75–87.5–1002508212,600
3,7002410×225–37.5–50–62.5–75–87.5–1002508213,860
4,2002460×225–37.5–50–62.5–75–87.5–1003008315,100

Catalogue figures at nominal conditions. Capacities in kW, water flows in m³/h, sound pressure measured 1 m in open field.

Features

  • Flooded evaporator, high-efficiency condenser
  • Large heat-transfer surface, high fouling factor
  • Partial or full heat recovery
  • Cupronickel or titanium exchanger option
  • Brine duty down to −7 °C

Typical applications

Large district heating and cooling, brine loops to −7 °C, industrial plants with a stable water source.