Main units · chillers & heat pumps

Main units · chillers & heat pumps
Water-source heat pump, M series
Series SGHP(M) · 600–4200. Cooling 535–3,664 kW, heating 577–4,189 kW. Semi-hermetic screw, R22, 380 V / 3 ph / 50 Hz.
Technical data
| Series & sizes | SGHP(M) · 600–4200 |
|---|---|
| Cooling capacity | 535–3,664 kW |
| Heating capacity | 577–4,189 kW |
| Water flow | 92–630 m³/h |
| Compressor | Semi-hermetic screw |
| Refrigerant | R22 |
| Power supply | 380 V / 3 ph / 50 Hz |
| Dimensions | L 3,560–5,410 · W 1,370–2,680 · H 1,470–3,235 mm |
| Weight | 5,000–15,100 kg |
Figures are catalogue data at nominal conditions. Confirm the exact model on the datasheet before ordering.
Model data
Cooling duty
Chilled water 12/7 °C · cooling water 18/29 °C| Size | Cooling capacitykW | Power input (cooling)kW | Load-side flowm³/h | Source-side flowm³/h |
|---|---|---|---|---|
| 600 | 535 | 91 | 92 | 49 |
| 800 | 722 | 116 | 124 | 66 |
| 1,000 | 887 | 148 | 153 | 81 |
| 1,200 | 1,071 | 182 | 184 | 98 |
| 1,600 | 1,445 | 232 | 248 | 131 |
| 2,000 | 1,774 | 296 | 305 | 162 |
| 3,100 | 2,723 | 444 | 468 | 248 |
| 3,700 | 3,206 | 520 | 551 | 291 |
| 4,200 | 3,664 | 588 | 630 | 332 |
Heating duty
Chilled water 15/7 °C · hot water 40/45.5 °C| Size | Heating capacitykW | Power input (heating)kW | Load-side flowm³/h | Source-side flowm³/h |
|---|---|---|---|---|
| 600 | 577 | 125 | 92 | 49 |
| 800 | 811 | 165 | 124 | 66 |
| 1,000 | 966 | 205 | 153 | 81 |
| 1,200 | 1,155 | 251 | 184 | 98 |
| 1,600 | 1,621 | 331 | 248 | 131 |
| 2,000 | 1,932 | 411 | 305 | 162 |
| 3,100 | 3,109 | 632 | 468 | 248 |
| 3,700 | 3,656 | 741 | 551 | 291 |
| 4,200 | 4,169 | 838 | 630 | 332 |
Unit data
Compressors, charge, steps, connections, sound and weight| Size | Compressors | Refrigerant chargekg | Capacity steps% | Pipe connectionsDN | Sound pressuredB(A) | Weightkg |
|---|---|---|---|---|---|---|
| 600 | 1 | 140 | 50–75–100 | 125 | 79 | 5,000 |
| 800 | 1 | 195 | 50–75–100 | 150 | 80 | 5,600 |
| 1,000 | 1 | 240 | 50–75–100 | 150 | 81 | 6,500 |
| 1,200 | 2 | 140×2 | 25–37.5–50–62.5–75–87.5–100 | 150 | 80 | 7,000 |
| 1,600 | 2 | 195×2 | 25–37.5–50–62.5–75–87.5–100 | 200 | 80 | 7,500 |
| 2,000 | 2 | 240×2 | 25–37.5–50–62.5–75–87.5–100 | 200 | 81 | 7,780 |
| 3,100 | 2 | 350×2 | 25–37.5–50–62.5–75–87.5–100 | 250 | 82 | 12,600 |
| 3,700 | 2 | 410×2 | 25–37.5–50–62.5–75–87.5–100 | 250 | 82 | 13,860 |
| 4,200 | 2 | 460×2 | 25–37.5–50–62.5–75–87.5–100 | 300 | 83 | 15,100 |
Catalogue figures at nominal conditions. Capacities in kW, water flows in m³/h, sound pressure measured 1 m in open field.
Features
- Flooded evaporator, high-efficiency condenser
- Large heat-transfer surface, high fouling factor
- Partial or full heat recovery
- Cupronickel or titanium exchanger option
- Brine duty down to −7 °C
Typical applications
Large district heating and cooling, brine loops to −7 °C, industrial plants with a stable water source.