Home Products Services About InsightsContact
Get a Quote
Main units · chillers & heat pumps
Ground-source heat pump SGHP(ML)
Main units · chillers & heat pumps

Ground-source heat pump

Series SGHP(ML) · 500–3000. Cooling 539–3,576 kW, heating 449–2,988 kW. Screw, 1–2 per unit, R22 · R134a optional, 380 V / 3 ph / 50 Hz · 460 V / 60 Hz optional.

Technical data

Series & sizesSGHP(ML) · 500–3000
Cooling capacity539–3,576 kW
Heating capacity449–2,988 kW
Water flow109–506 m³/h
Source-side flow93–630 m³/h
CompressorScrew, 1–2 per unit
RefrigerantR22 · R134a optional
Power supply380 V / 3 ph / 50 Hz · 460 V / 60 Hz optional
Weight5,000–15,100 kg
Sound pressure79–83 dB(A)

Figures are catalogue data at nominal conditions. Confirm the exact model on the datasheet before ordering.

Model data

Cooling duty

Chilled water 12/7 °C · source water 25/30 °C
SizeCooling capacitykWPower input (cooling)kWLoad-side flowm³/hSource-side flowm³/hCompressors
50053995931091
6006991251201371
8008571591471751
10001,0781901862182
12001,3982502402842
16001,7143182943502
23002,6584784573752
27003,1305585384432
30003,5766326155062

Heating duty

Chilled water 0/−2.66 °C · hot water 40/44.2 °C · 25–30% glycol on the source side
SizeHeating capacitykWPower input (heating)kWLoad-side flowm³/hSource-side flowm³/h
50044911393109
600584149120142
800726189147175
1000898226186218
12001,168298240284
16001,452378294350
23002,230572457375
27002,622670538443
30002,988756615506

Unit data

Charge, regulation, sound and weight per size
SizeRefrigerant chargekgCapacity steps%Sound pressuredB(A)WeightkgPipe connectionsDN
50014050–75–100795,000100
60019550–75–100805,600150
80024050–75–100816,500150
1000140×225–37.5–50–62.5–75–87.5–100807,000150
1200195×225–37.5–50–62.5–75–87.5–100817,500200
1600240×225–37.5–50–62.5–75–87.5–100827,780200
2300350×225–37.5–50–62.5–75–87.5–1008212,600250
2700410×225–37.5–50–62.5–75–87.5–1008313,860250
3000460×225–37.5–50–62.5–75–87.5–1008315,100300

Catalogue figures at nominal conditions. Capacities in kW, water flows in m³/h, sound pressure measured 1 m in open field.

Features

  • Flooded evaporator, high-efficiency condenser
  • Large heat-transfer surface, high fouling factor
  • Partial or full heat recovery
  • Cupronickel or titanium exchanger option
  • Brine duty down to −7 °C

Typical applications

Ground and groundwater loops at low source temperature, district heating and cooling, industrial waste heat, boiler replacement.