Main units · chillers & heat pumps

Main units · chillers & heat pumps
Water-source heat pump, A series
Series SGHPA · 260–2200. Cooling 218–1,833 kW, heating 255–2,258 kW. Semi-hermetic screw, R407C, 380 V / 3 ph / 50 Hz.
Technical data
| Series & sizes | SGHPA · 260–2200 |
|---|---|
| Cooling capacity | 218–1,833 kW |
| Heating capacity | 255–2,258 kW |
| Water flow | 37–315 m³/h |
| Compressor | Semi-hermetic screw |
| Refrigerant | R407C |
| Power supply | 380 V / 3 ph / 50 Hz |
| Dimensions | L 3,050–4,635 · W 1,175–1,520 · H 1,400–1,710 mm |
| Weight | 1,500–6,350 kg |
Figures are catalogue data at nominal conditions. Confirm the exact model on the datasheet before ordering.
Model data
Cooling duty
Chilled water 12/7 °C · cooling water 18/29 °C| Size | Cooling capacitykW | Power input (cooling)kW | Load-side flowm³/h | Source-side flowm³/h |
|---|---|---|---|---|
| 260 | 218 | 46 | 37 | 21 |
| 300 | 267 | 56 | 46 | 25 |
| 350 | 278 | 62 | 48 | 27 |
| 450 | 367 | 80 | 63 | 35 |
| 500 | 428 | 87 | 74 | 40 |
| 550 | 479 | 98 | 82 | 45 |
| 600 | 517 | 102 | 89 | 48 |
| 680 | 563 | 121 | 97 | 53 |
| 780 | 675 | 134 | 116 | 63 |
| 880 | 716 | 148 | 123 | 68 |
| 980 | 837 | 173 | 144 | 79 |
| 1,000 | 865 | 176 | 149 | 81 |
| 1,080 | 880 | 188 | 151 | 83 |
| 1,200 | 1,059 | 207 | 182 | 96 |
| 1,380 | 1,156 | 248 | 199 | 110 |
| 1,500 | 1,262 | 248 | 217 | 118 |
| 1,600 | 1,391 | 278 | 239 | 130 |
| 1,700 | 1,460 | 302 | 251 | 138 |
| 1,900 | 1,680 | 347 | 289 | 158 |
| 2,000 | 1,731 | 356 | 298 | 163 |
| 2,200 | 1,833 | 389 | 315 | 174 |
Heating duty
Chilled water 15/7 °C · hot water 40/45.5 °C| Size | Heating capacitykW | Power input (heating)kW | Load-side flowm³/h | Source-side flowm³/h |
|---|---|---|---|---|
| 260 | 255 | 62 | 37 | 21 |
| 300 | 318 | 80 | 46 | 25 |
| 350 | 337 | 82 | 48 | 27 |
| 450 | 447 | 109 | 63 | 35 |
| 500 | 495 | 120 | 74 | 40 |
| 550 | 556 | 134 | 82 | 45 |
| 600 | 598 | 141 | 89 | 48 |
| 680 | 681 | 164 | 97 | 53 |
| 780 | 783 | 186 | 116 | 63 |
| 880 | 850 | 201 | 123 | 68 |
| 980 | 977 | 240 | 144 | 79 |
| 1,000 | 1,010 | 244 | 149 | 81 |
| 1,080 | 1,075 | 258 | 151 | 83 |
| 1,200 | 1,228 | 290 | 182 | 96 |
| 1,380 | 1,399 | 336 | 199 | 110 |
| 1,500 | 1,460 | 345 | 217 | 118 |
| 1,600 | 1,618 | 385 | 239 | 130 |
| 1,700 | 1,738 | 408 | 251 | 138 |
| 1,900 | 1,970 | 483 | 289 | 158 |
| 2,000 | 2,029 | 496 | 298 | 163 |
| 2,200 | 2,258 | 538 | 315 | 174 |
Unit data
Charge, pipe connections and sound pressure per size| Size | Refrigerant chargekg | Pipe connectionsDN | Sound pressuredB(A) |
|---|---|---|---|
| 260 | 35 | 80/80 | 77 |
| 300 | 45 | 80/80 | 77 |
| 350 | 55 | 80/80 | 78 |
| 450 | 65 | 100/100 | 78 |
| 500 | 75 | 100/100 | 79 |
| 550 | 80 | 125/125 | 80 |
| 600 | 85 | 125/125 | 80 |
| 680 | 90 | 125/125 | 81 |
| 780 | 110 | 150/125 | 81 |
| 880 | 120 | 150/150 | 82 |
| 980 | 130 | 150/150 | 82 |
| 1,000 | 150 | 150/150 | 79 |
| 1,080 | 160 | 150/150 | 80 |
| 1,200 | 170 | 150/150 | 80 |
| 1,380 | 180 | 150/150 | 81 |
| 1,500 | 200 | 150/150 | 81 |
| 1,600 | 220 | 200/150 | 82 |
| 1,700 | 240 | 200/200 | 82 |
| 1,900 | 260 | 200/200 | 82 |
| 2,000 | 270 | 200/200 | 83 |
| 2,200 | 320 | 200/200 | 83 |
Catalogue figures at nominal conditions. Capacities in kW, water flows in m³/h, sound pressure measured 1 m in open field.
Features
- Shell-and-tube heat exchangers
- Large heat-transfer surface, high fouling factor
- Partial or full heat recovery
- Cupronickel or titanium exchanger option
- Microprocessor control with remote access
Typical applications
Groundwater and surface-water loops, river or lake cooling, industrial process water heating.