Main units · chillers & heat pumps

Main units · chillers & heat pumps
High-temperature hot water heat pump
Series GSHP(HT / HS) · 140–1500. Heating 145–1,480 kW. Semi-hermetic screw, CD-1 (non-flammable), 380 V / 3 ph / 50 Hz.
Technical data
| Series & sizes | GSHP(HT / HS) · 140–1500 |
|---|---|
| Heating capacity | 145–1,480 kW |
| Hot water outlet | 75 °C (HT) · 85 °C (HS) |
| Water flow | 25–255 m³/h |
| Source-side flow | 17–183 m³/h |
| Compressor | Semi-hermetic screw |
| Refrigerant | CD-1 (non-flammable) |
| Power supply | 380 V / 3 ph / 50 Hz |
| Dimensions | L 2,100–3,570 · H 1,445–2,014 mm |
| Weight | 1,800–9,000 kg |
Figures are catalogue data at nominal conditions. Confirm the exact model on the datasheet before ordering.
Model data
Heating duty
Source water 43/38 °C · hot water 70/75 °C · compressor CD-1| Size | Heating capacitykW | Power input (heating)kW | Load-side flowm³/h | Source-side flowm³/h | Compressors |
|---|---|---|---|---|---|
| 140 | 145 | 44.3 | 25 | 17 | 1 |
| 220 | 220 | 65.7 | 38 | 27 | 1 |
| 300 | 315 | 91.7 | 54 | 39 | 1 |
| 440 | 444 | 132.5 | 77 | 54 | 1 |
| 500 | 520 | 147 | 90 | 64 | 2 |
| 700 | 740 | 216.9 | 128 | 90 | 2 |
| 900 | 950 | 294.8 | 164 | 113 | 2 |
| 1,000 | 1,150 | 325 | 198 | 142 | 2 |
| 1,500 | 1,480 | 417 | 255 | 183 | 2 |
Unit data
Charge, capacity steps, connections, sound and weight| Size | Refrigerant chargekg | Capacity steps% | Pipe connectionsDN | Sound pressuredB(A) | Weightkg |
|---|---|---|---|---|---|
| 140 | 46 | 25–50–75–100 | 65 | 80 | 1,800 |
| 220 | 70 | 25–50–75–100 | 80 | 81 | 2,250 |
| 300 | 97 | 25–50–75–100 | 100 | 82 | 2,836 |
| 440 | 140 | 25–50–75–100 | 125 | 83 | 3,250 |
| 500 | 171 | 12.5–25–37.5–50–62.5–75–87.5–100 | 125 | 81 | 3,580 |
| 700 | 222 | 12.5–25–37.5–50–62.5–75–87.5–100 | 150 | 82 | 4,500 |
| 900 | 302 | 12.5–25–37.5–50–62.5–75–87.5–100 | 150 | 82 | 5,500 |
| 1,000 | 380 | 12.5–25–37.5–50–62.5–75–87.5–100 | 150 | 83 | 6,800 |
| 1,500 | 500 | 12.5–25–37.5–50–62.5–75–87.5–100 | 2×125 | 83 | 9,000 |
Catalogue figures at nominal conditions. Capacities in kW, water flows in m³/h, sound pressure measured 1 m in open field.
Features
- Hot water up to 85 °C
- Anti-corrosion casing and coil options
- Spring / rubber vibration isolators
- Microprocessor control with remote access
- Electronic expansion valve
Typical applications
Replacing coal and gas boilers, radiator retrofit, district heating return-water boost, food and textile process heat.